Simplicity SE Control Board Navigation
Components
The following components are needed to access the control
points in the Simplicity® SE control. Installation and operation
guides are located on www.upgnet.com under Product Center \
Equipment Catalog \ Commercial Products \ Zoning Systems
and Controls.
1. Local LCD on Unit Control Board.
OR
2. Mobile Access Portal (MAP) Gateway (Portable).
Source 1 P/N S1-JC-MAP1810-OP
3. MAP Gateway Quick Start Guide P/N 24-10737-16
4. MAP Gateway Instruction P/N 24-10737-8
NOTE: For more in-depth sequence of operation of the
Simplicity® SE control please refer to 5127915 on
www.upgnet.com under Product Center \ Equipment
Catalog \ Commercial Products \ Zoning Systems and
Controls. www.upgnet.com under Product Center \
Equipment Catalog \ Commercial Products \ Zoning
Systems and Controls.
Table 30: Unit Control Board Flash Codes
Flash Code Description
On Steady Control Failure - Replace Control
Heart Beat Normal Operation
1 Flash Not Applicable
2 Flashes Control waiting ASCD
1
1. These flash codes do not represent alarms.
3 Flashes HPS1 - Compressor Lock out
5 Flashes LPS1 - Compressor Lock out
7 Flashes FS1 - Compressor Lock out
9 Flashes
Ignition Control Locked Out/
Ignition Control Failure / Limit Switch Trip / No
Jumper Plug in Heat Section
10 Flashes
Compressors Locked Out On Low
Outdoor Air Temperature
1
11 Flashes
Compressors Locked Out Because The
Economizer Is Using Free Cooling
1
13 Flashes Compressor Held Off Due To Low Voltage
1
14 Flashes EEPROM Storage Failure (Control Failure)
OFF No Power or Control Failure
Table 31: Ignition Control Board Flash Codes
Flash Code Description
Heart Beat Normal Operation
1 Flash Not Applicable
2 Flashes Pressure / Centrifugal Switch Open with Inducer On
3 Flashes
Pressure / Centrifugal Switch Closed with Inducer
Off
4 Flashes Not Applicable
5 Flashes Lock Out From Too Many Flame Losses
6 Flashes High Temperature Switch Open (Primary or Aux.)
7 Flashes Rollout Switch Open
8 Flashes Flame Present With Gas Off
9 Flashes Gas Valve Stuck Off or On
10 Flashes Flame Sense Circuit Failure
Table 31: Ignition Control Board Flash Codes
Flash Code Description