697890-YIM-C-0213
26 Johnson Controls Unitary Products
060
(5.0)
208-1-60
21.1 105.0 33.0 2.3 7.6 10.0
None - - - 46.3 60
E05 4.0 1 19.2 46.3 60
E07 5.6 1 26.9 55.7 60
E10 8.0 1 38.5 70.1 80
E15 11.9 2 57.2 93.5 100
E20 15.9 2 76.4 117.6 125
E30 22.2 2 106.7 155.4 175
230-1-60 21.1 105.0 33.0 2.3 7.6 10.0
None - - - 46.3 60
E05 5.3 1 22.1 49.6 60
E07 7.5 1 31.3 61.1 70
E10 10.6 1 44.2 77.2 80
E15 15.9 2 66.3 104.8 110
E20 21.2 2 88.3 132.4 150
E30 29.6 2 123.3 176.2 200
208-3-60
14.1 88.0 22.0 2.3 5.2 10.0
None - - - 35.1 45
E05 4.0 1 11.1 35.1 45
E07 5.6 1 15.5 38.4 45
E10 8.0 1 22.2 46.8 50
E15 11.9 2 33.0 60.3 70
E20 15.9 2 44.1 74.2 80
E30 22.2 2 61.6 96.0 100
230-3-60 14.1 88.0 22.0 2.3 5.2 10.0
None - - - 35.1 45
E05 5.3 1 12.7 35.1 45
E07 7.5 1 18.0 41.6 45
E10 10.6 1 25.5 50.9 60
E15 15.9 2 38.2 66.8 70
E20 21.2 2 51.0 82.7 90
E30 29.6 2 71.2 108.0 110
460-3-60
7.7 55.0 12.0 1.3 2.6 5.0
None - - - 18.5 25
E07 6.8 1 8.2 19.7 25
E10 10.1 1 12.1 24.7 25
E15 13.6 2 16.4 29.9 30
E20 19.5 2 23.5 38.8 40
E30 28.8 2 34.6 52.8 60
575-3-60 4.8 36.0 7.5 1.3 2.0 4.0
None - - - 13.0 15
E10 10.6 1 10.2 20.2 25
E15 15.9 1 15.3 26.6 30
E20 21.2 2 20.4 33.0 35
E30 30.4 2 29.3 44.1 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF036-060 - With Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps

Table of Contents