1088917-YIM-B-1014
Johnson Controls Unitary Products 27
Optional Electric Heat
The factory-installed heaters are wired for single point power
supply. Power supply need only be brought into the single point
terminal block.
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending in
to the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and others do not. refer to Table 10 for
minimum CFM limitations and to Table 8 for electrical data.
CONDENSER FAN DATA
Quantity 2 2 2 2
Fan diameter (Inch) 30 24 30 30
Type Prop Prop Prop Prop
Drive type Direct Direct Direct Direct
No. speeds 1 1 1 1
Number of motors 2 2 2 2
Motor HP each 1.25 1.25 1.25 1.25
RPM 1140 1140 1140 1140
Total CFM 11530 14000 14000 14000
BELT DRIVE EVAP FAN DATA
Quantity 1 1 1 1
Fan Size (Inch) 15 X 15 18 X 15 18 X 15 18 X 15
Type Centrifugal Centrifugal Centrifugal Centrifugal
Motor Sheave 1VP65 1VP65 1VP60 1VP60 1VP60 1VP60 1VP60 1VP75X 1VP75X
Blower Sheave BK110 BK090 BK110 BK090 BK110 BK090 1B5V94 1B5V110 1B5V94
Belt BX75 BX70 BX78 BX75 BX78 BX75 BX78 5VX840 5VX860
Motor HP each 5 5 5 7.5 5 7.5 7.5 10 15
RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725
Frame size 184T 184T 184T 213T 184T 213T 213T 215T 254T
FILTERS
Quantity - Size
5 - (18 x 24 x 2)
1,2
12 - (12 x 24 x 2)
1,2
4 - (16 x 25 x 2), 12 - (12 x 24 x 2)
1,2
- - 4 - (16 x 20 x 2)
1,2
-
5 - (18 x 24 x 4)
3
2 - (20 x 24 x 4), 4 - (16 x 25 x 4), 2 - (20 x 24 x 4),
- 4 - (24 x 24 x 4)
3
4 - (16 x 20 x 4)
3
4 - (24 x 24 x 4)
3
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
Table 9: ZF180-300 Physical Data (Continued)
Component
Models
ZF180 ZF210 ZF240 ZF300
Nominal Tonnage 15 17.5 20 25
Table 10: Electric Heat Minimum Supply Air
Size
(Tons)
Voltage
Minimum Supply Air (CFM)
Heater kW
9185472
180
(15)
208/230-3-60 4500 4500 5000 5000
460-3-60 4500 4500 5000 4500
600-3-60 4500 4500 4500 4500
210
(17.5)
208/230-3-60 6000 6000 6000 6000
460-3-60 6000 6000 6000 6000
600-3-60 6000 6000 6000 6000
240
(20)
208/230-3-60 6000 6000 6000 6000
460-3-60 6000 6000 6000 6000
600-3-60 6000 6000 6000 6000
300
(25)
208/230-3-60 7500 7500 7500 7500
460-3-60 7500 7500 7500 7500
600-3-60 7500 7500 7500 7500