York ZW Series - ZWTA3 Thru TA5 Unit Physical Dimensions; ZWTA3 Thru TA5 Unit Clearances

York ZW Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5803642-TIM-B-0620
Johnson Controls Ducted Systems 11
Detail A Detail B
Table 4: ZWTA3 thru TA5 Unit Physical Dimensions
Unit Model Number
Dimension (in.)
ABCDEF
ZWTA3 42 89 22 1/8 18 3/16 15 3/16 6 3/16
ZWTA4 42 89 22 1/8 18 3/16 15 3/16 6 3/16
ZWTA5 42 89 22 1/8 18 3/16 15 3/16 6 3/16
42” CABINET
Ø 3.126
Ø 2.000
3.184
4.727
7.705
14.594
Gas Pipe Inlet
Gas Exhaust Vent
5-3/8
1” FPT
Table 5: ZWTA3 thru TA5 Unit Clearances
Direction Distance (in.) Direction Distance (in.)
Top
1
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
72 Right 12
Front 36 Left 36
Rear 36 Bottom
2
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
0