EN- 13
3.3 Frost protection (P52)
The unit with pre heater has a
frost protection which can be
set in menu P52 in to 4
settings.
The default setting is 2: Nominal protection.
In cold areas (frequent periods of -10°C or lower),
where the pre heater must switch on sooner, the
setting can be set to 0: Extreme protection or 1: High
protection.
In warmer areas, where the pre heater does not have
to switch on so soon, the setting can be set to 3:
Economy.
3.4 Fire place program (P50)
When a fire place is present in
the dwelling the open fire
program must be activated.
This must be done in menu
P50.
The default setting is 0: open fire program not active.
The open fire program can activated by setting the
menu P50 to 1: open fire program active.
3.5 Enthalpy exchanger (P59)
The presence of a enthalpy
exchanger must be given in
menu P59.
The default setting is 0; Enthalpy exchanger not
fitted.
When a enthalpy exchanger is installed this menu
must be set to 2; Enthalpy exchanger without RH
sensor. When the unit is delivered from factory with
enthalpy exchanger the standard setting is already
changed to 2.
Ensure the condensation drain is sealed.