12 - EN
EN- 13
3.3 Frost protection (P52)
The unit with pre heater has a
frost protection which can be
set in menu P52 in to 4
settings.
The default setting is 2: Nominal protection.
In cold areas (frequent periods of -10°C or lower),
where the pre heater must switch on sooner, the
setting can be set to 0: Extreme protection or 1: High
protection.
In warmer areas, where the pre heater does not have
to switch on so soon, the setting can be set to 3:
Economy.
3.4 Fire place program (P50)
When a fire place is present in
the dwelling the open fire
program must be activated.
This must be done in menu
P50.
The default setting is 0: open fire program not active.
The open fire program can activated by setting the
menu P50 to 1: open fire program active.
3.5 Enthalpy exchanger (P59)
The presence of a enthalpy
exchanger must be given in
menu P59.
The default setting is 0; Enthalpy exchanger not
fitted.
When a enthalpy exchanger is installed this menu
must be set to 2; Enthalpy exchanger without RH
sensor. When the unit is delivered from factory with
enthalpy exchanger the standard setting is already
changed to 2.
Ensure the condensation drain is sealed.

Other manuals for Zehnder Rittling ComfoAir 180

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Zehnder Rittling ComfoAir 180 and is the answer not in the manual?

Zehnder Rittling ComfoAir 180 Specifications

General IconGeneral
BrandZehnder Rittling
ModelComfoAir 180
CategoryFan
LanguageEnglish

Related product manuals