8
Putting into use
■ Open valves carefully and check installation for
leakage.
■ If the sleep mode of the counter is enabled
(Display: SLEEP 1), then it must be deactivat-
ed by longer pressing the button (>5s).
■ While the system is operating, check whether
the volume display advances and the tem-
peratures displayed correspond with the actual
temperatures (see the display overview).
■ Wait for the temperature display to be updated
(1-2 sec).
■ Secure meter with the enclosed sealing mate-
rial against unauthorised removal.
■ Fill in the putting into use report in accordance
with PTB-Directive TR K9.
Consumer
Asymmetrical sensor installation for zelsius
®
C5-ISF with the return
sensor integrated in the flow sensor
Supply
Return
Consumer
Symmetrical sensor installation for zelsius
®
C5-ISF
Supply
Return
Consumer
Asymmetrical sensor installation for zelsius
®
C5-ISF with the return
sensor integrated in the flow sensor
Supply
Return
Consumer
Symmetrical sensor installation for zelsius
®
C5-ISF
Supply
Return
Note relating to the mounting in existing im-
mersion sleeves:
The device C5 can be put into use in connection
with existing immersion sleeves in accordance
with the article “Putting into use of MID homolo-
gated temperature sensors” released in the PTB
notications 119 (2009), vol.6.
Based on current information, the regulation has
a period of validity until 30.10.2016. For the iden-
tication
and marking of the usable existing immersion
sleeves in connection with the C5 device, an
identication and marking set can be delivered
from our company.