EDA-Z5008, Z5020 & Z5100 Technical Manual ZPControlTechMan_r105
_____________________________________________________________________________________________________
7
1.0 - EN54 Approved Configuration
The Zerio Plus system has been approved by Intertek to meet EN54 parts 2 and 4. The panels were
tested and approved in their default configuration. This manual lists all available panel options and
settings, some of which can be set in a way that would result in a system that does not comply with
EN54. The EN54 approved settings are listed below:
Setup Type: Standard
Test Mode Type: By Zone
Test Mode Timeout: 0
Relay 1: Fire Routing Relay
Relay 2: Fault Relay safe
Relay 3: Sounder circuit
Relay 4: Sounder circuit
Relays: FIRE & SOUNDERS ON
Panel Buzzer: Enabled
Code Protect: ON
Device Verify Time: 390 seconds or less
Sounder Tone: Swept
Input Type: Latching
Input Relay Options: Relays Off
Fire & Sounders On
Heat Detector Type: A1S
Fault Relay: Enabled
Device Faults: Enabled
Panel Faults: Enabled