VFD frequency setting method selection
The VFD frequency setting mode of the VFD is set by parameter F0.05.
When F0.05=4, the running frequency is set by the potentiometer; when
F0.05=2, the running frequency is input by AVI (0-10V can be connected
to a potentiometer); when F0.05=3, the running frequency is input by ACI
(4-20mA); when F0.05=1, it is controlled by the external terminal (the
digital value is set to increase/decrease the frequency).