Why ZIEHL-ABEGG Fan does not run anymore?
- DDaniel StanleyAug 7, 2025
If your ZIEHL-ABEGG Fan has stopped running, several factors could be responsible. It could be due to: * No line voltage or a line failure: In this case, check the line voltage. * An earth fault: Inspect the motor connection and line voltage. * A short circuit winding: Replacement of the motor / fan is required. * The thermal motor protection has triggered because the motor is overheated: Ensure free air passages, remove any obstructions, and check the supply air temperature. For single-phase motors, verify the capacitor. * The impeller is blocked or dirty: Turn off the power, ensure safe isolation, remove the safety grille, clear any foreign objects or dirt, remount the grille, and proceed with the start-up procedure.