Do you have a question about the ZIEHL-ABEGG UNIcon CPG-6000AVC and is the answer not in the manual?
Housing material | Plastic |
---|---|
Connection type | Screw terminals |
Ambient temperature | -20 °C to +50 °C |
Storage temperature | +70 °C |
Relative humidity | 5 % to 95 %, non-condensing |
Protocol | Modbus RTU |
Emphasizes critical safety precautions for installation, operation, and maintenance by qualified personnel.
Defines the device's purpose for measured value acquisition of differential pressures with non-aggressive gases.
Advises maintaining distance from powerlines and motor wires to prevent interference and proper shield connection.
Details the connection for supply voltage at '+Us' and 'GND' terminals, emphasizing PELV sources.
Explains the connection for the 0...10 V output signal to terminals 'A' and 'GND' and parallel control of multiple devices.
Explains the RS-485 interface connection for networking via MODBUS, specifying terminals A, B, and GND.
Describes the process of automatic addressing for MODBUS networks using ID1 and ID2 connections.
Explains how to select pre-programmed operating modes (e.g., 4.00, 4.01) to define the device's basic function.
Outlines the procedure for device start-up, including mounting, connection checks, and setting parameters.
Covers programming for pressure sensor and control functions, including base setup and operation settings.
Details specific operational settings for pressure control modes, such as setpoint, Pband, and output voltage.
Covers programming for volume sensor and control functions, including base setup and conversion factors.
Details specific operational settings for volume flow control modes, including setpoint, Pband, and output voltage.
Introduces the MODBUS SLAVE interface for networking with master building control systems using the MODBUS-RTU protocol.
Explains the MODBUS register map, detailing holding registers for device configuration and control.