INSTALLATION AND
OPERATION MANUAL
ENGLISH
WARNING
FOR YOUR SAFETY: This product must be installed and serviced by a contractor who is gas safe registered and
HWB1 certified. Before installing this product, read and follow all warning notices and instructions that accompany
this product. Failure to follow warning notices and instructions may result in property damage, personal injury, or
death. Improper installation and/or operation can create carbon monoxide gas and flue gases which can cause
serious injury, property damage, or death. For indoor installations, as an additional measure of safety, Zodiac
Pool Systems, Inc. strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this
appliance and in any adjacent occupied spaces. Improper installation and/or operation will void the warranty.
If these instructions are not followed exactly, a fire or explosion may result,
causing property damage, personal injury, or death.
H0316500 Rev F
WARNING
The GAS SAFETY (INSTALLATION AND USE) REGULATIONS 1998 as amended, place statutory requirements
on gas users.
This heater is certified to European requirements for use only as a swimming pool or spa heater. The heater must
not be used for any other purpose and must be installed and serviced by a qualified professional. The heater must
be operated strictly in accordance with the user's instructions and applicable laws.
If the heater is installed in a room, it must be separated from a living space, and adequate air supply and
ventilation must be provided and maintained.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Read this manual in its entirety. If these instructions are not followed exactly,
a fire or explosion may result, causing property damage, personal injury, or death.
Installation and
Operation Manual
Legacy™
Pool and Spa Heater
Model LRZ Millivolt
Natural Gas or LPG

Table of Contents

Questions and Answers

  • W
    William PriceAug 18, 2025
    How to troubleshoot pump not operating in Zodiac Swimming Pool Heater?
    • J
      jdavisAug 18, 2025
      If your Zodiac Swimming Pool Heater's pump isn't working, here are a few things to check: * **No Power:** Make sure the circuit breakers are on and the power source is working. * **Defective Pump:** If there's power, the pump itself might be broken and need replacement. * **Wiring:** Double-check the wiring to be sure it's correct.
  • K
    knightvincentAug 21, 2025
    Why is there flame roll-out at start-up with my Zodiac Swimming Pool Heater?
    • M
      Mrs. Kathy BassAug 21, 2025
      Flame roll-out at start-up in your Zodiac Swimming Pool Heater can occur due to: * A blocked flue. Clear the blockage. * A pilot out of position. Correct the pilot position. * A blocked heat exchanger. Clean and correct as necessary. * A refractory blanket out of place. Clean and correct the blanket as necessary. * An altered vent cap. Install an unaltered factory approved vent cap. * Low gas pressure. Check and correct the gas pressure.
  • C
    Corey KimAug 25, 2025
    What causes pilot outage in Zodiac Legacy LRZ?
    • A
      Anthony MelendezAug 25, 2025
      Pilot outage in your Zodiac Swimming Pool Heater can be caused by several factors: * **Low Inlet Gas Pressure:** Consult your gas utility company. Ensure the inlet gas pressure to the heater is within the range of 13.7 to 24.9 mbar for natural gas or 24.9 to 34.8 mbar for propane gas. * **High Inlet Gas Pressure:** Pressure should be regulated within the specified limits. * **Weak or Defective Thermocouple/Thermopile:** Replace the thermocouple or thermopile. * **Damaged Pilot Components:** Replace any damaged pilot, thermocouple, or thermopile. * **Dirty Pilot:** Blow dust or lint out of the pilot. * **Plugged or Undersized Pilot Orifice:** Clean or replace the pilot orifice. * **Plugged Burner Orifices:** Remove and clean all burner orifices.
  • M
    marcusandersonAug 27, 2025
    Why is there spillage at draft hood of my Zodiac Legacy LRZ Swimming Pool Heater?
    • P
      Pamela BrownAug 28, 2025
      Spillage at the draft hood of your Zodiac Swimming Pool Heater can happen because of: * A cold chimney. Allow the heater to run for five minutes to establish draft action. * A vent pipe that slopes downward toward the chimney. Reinstall the vent pipe so it slopes upwards from the heater to the chimney. * A blocked chimney. Clear the blockage. * An altered draft hood. Install a factory-provided draft hood. * A prefabricated chimney with an incorrect cap. Install a U.L. listed vent cap.
  • E
    elizabeth21Aug 30, 2025
    Why is my Zodiac Legacy LRZ Swimming Pool Heater not producing enough heat?
    • J
      Jeremy WheelerAug 30, 2025
      If your Zodiac Swimming Pool Heater isn't producing enough heat, consider the following: * **Inadequate Gas Supply:** The gas meter or the gas line from the meter to the heater might be too small. * **Low Burner Gas Pressure:** Adjust the gas pressure on the heater burner to the values listed in Table 2. * **Inadequate Heater Size:** You may need to replace the heater with one that has a higher input. * **Low Temperature Rise:** Check and correct the water flow.
  • B
    bellmelissaSep 2, 2025
    What causes lazy flame with yellow tip in Zodiac Legacy LRZ?
    • T
      tiffanyrichardsonSep 2, 2025
      A lazy flame with a yellow tip in your Zodiac Swimming Pool Heater could be due to: * Low primary air. Check for internal burner obstructions. * Incorrect burner pressure. Adjust burner pressure according to the rating plate and clean burner ports if they are dirty.
  • A
    Anthony HoltSep 6, 2025
    Why is my Zodiac Legacy LRZ Swimming Pool Heater pounding or knocking?
    • K
      Kristi WhiteSep 6, 2025
      Heater pounding or knocking in your Zodiac Swimming Pool Heater can be caused by inadequate water flow through the heater. Check the temperature rise between the inlet and outlet heater piping. If the temperature rise is above the recommended maximum (see section 11.6), check for a closed valve in the system.
  • D
    Deborah TorresSep 8, 2025
    Why is my Zodiac Legacy LRZ condensing?
    • D
      Dr. Kathy ThorntonSep 8, 2025
      Condensation in your Zodiac Swimming Pool Heater is often due to low water temperature. Flue product moisture will condense at start-up until the heater water reaches normal operating temperature.
  • D
    David EdwardsSep 12, 2025
    What to do if pressure relief valve opens on my Zodiac Legacy LRZ?
    • T
      taylorguySep 12, 2025
      If the pressure relief valve on your Zodiac Swimming Pool Heater opens, it could indicate a restriction in the water flow system at or downstream of the heater. Check the operation of all valves, the bypass valve, and any equipment between the pool and the heater outlet.
  • D
    Daniel GayNov 14, 2025
    What to do if pilot is lit but main burners will not come on in my Zodiac Legacy LRZ Swimming Pool Heater?
    • A
      Anna SmithNov 15, 2025
      If the pilot light is on but the main burners of your Zodiac Swimming Pool Heater won't ignite, here are several potential causes and solutions: * Ensure the gas valve is in the “on” position. * If hi-limit switches have failed, determine the reason for overheating and replace them. * For a failed or misadjusted pressure switch, adjust it (see Section 11.5) or replace it. * If the roll-out switch (fusible link) has failed, find the reason for the flame rollout and replace the switch. * A failed gas valve should be checked and replaced if necessary. * Check the thermostat circuit for broken wires or a defective thermostat by testing continuity with the wires disconnected. * Verify the heater wiring against the diagram in Section 6, correcting any errors. * For a failed vent...

Summary

General Information

Consumer Safety & Saving Tips

Safety rules for spa/hot tub use and energy saving tips for swimming pools.

Installation Instructions

2.1 Introduction & Requirements

General installation requirements, statutory information, and site preparation.

2.5 Location Requirements

Guidelines for selecting installation location, clearances, and flooring.

Gas Connections

4.1 Gas Supply and Piping

Instructions for connecting gas supply and proper piping practices.

4.2 Burner Pressure Adjustment

Procedures for checking and adjusting burner gas pressure for optimal performance.

Electrical

6.1 Main Power & 6.2 Earth Bonding

Details on power sources and essential earth bonding procedures for safety.

Commissioning

7.1 Heater Start-Up

Step-by-step guide for starting up the heater after installation and testing.

Operating Instructions

8.3 Lighting and Shutdown Procedures

Detailed procedures for lighting, operating, and shutting down the heater.

Maintenance

Troubleshooting

10.1 General Heater Troubleshooting

Common problems, causes, and solutions encountered during heater operation.

Professional Maintenance and Service

11.4 Electrical Troubleshooting

Procedures for diagnosing electrical faults in the heater system using a voltmeter.

Zodiac Legacy LRZ Specifications

General IconGeneral
CategorySwimming Pool Heater
BrandZodiac
ModelLegacy LRZ
Fuel TypeNatural Gas or Propane
Heating Capacity400, 000 BTU/hr
Ignition TypeElectronic