ZXDU68B201ProductDescription
S.N.ComponentDescription
5-48Vbusbar(-48V)-
6Workinggroundbusbar
(+/RTN)
Connects+/RTNcablesofbatterypacksandDCloads.
7ACinputconnection
terminals(L,N,L,N,
PE)
ConnectACinputcables(L,N,L,N,PE).
Caution:Itisrecommendedtocongurea50Acircuitbreaker
foreachACinputbranchtoprovideACinputpowerforthe
ZXDU68B201system.
2.2ZXD3000Rectier
TheZXD3000(V5.0)rectiersconvertACtoDC,powerDCloadsandchargethebatteries.
Appearance
FortheappearanceoftheZXD3000rectier,seeFigure2-3.
Figure2-3RectierAppearance
1.Fan2.Indicators3.QUY(query)button
ButtonsandIndicators
lPressandholdtheQUYbuttonofarectierfor5secondsandthentheCSUdisplays
therectier’smaininformationscreen.
lTheindicatorsdisplaytheoperationalstatusoftherectier.Foradescriptionofthe
indicators,refertoTable2-3.
Table2-3RectierOperationalStatus
Indicator
PowerRun
Alarm
Fault
OperationalStatus
LitLit-NotlitOperatingwithStable
Voltage
FlashingNotlit-NotlitSleep
LitFlashing-NotlitOutputCurrentLimit
2-4
SJ-20120703093141-002|2013-01-08(R1.2)ZTEProprietaryandCondential