Function name Signal type Signal name Description
DSTPDIS.1.2 EARTH_FLT GFC Record data of bank 2 for earth-
fault, GFC
DSTPDIS.1.3 EARTH_FLT GFC Record data of bank 3 for earth-
fault, GFC
DSTPDIS.1.1 XC_FLT GFC Record data of bank 1 for cross
country fault, GFC
DSTPDIS.1.2 XC_FLT GFC Record data of bank 2 for cross
country fault, GFC
DSTPDIS.1.3 XC_FLT GFC Record data of bank 3 for cross
country fault, GFC
High impedance based
restricted earth-fault
(HREFPDIF)
Binary inputs HREFPDIF.1.START High impedance restricted
earth-fault protection start
HREFPDIF.1.OPERATE High impedance restricted
earth-fault protection operate
Three-phase voltage (phase-to-
earth voltages) (RMS)
(VPHMMXU)
Analog inputs VPHMMXU.1.U_DB_A Phase A amplitude, magnitude
of reported value
VPHMMXU.1.U_DB_B Phase B amplitude, magnitude
of reported value
VPHMMXU.1.U_DB_C Phase C amplitude, magnitude
of reported value
VPHMMXU.1.U_ANGL_A Phase A angle
VPHMMXU.1.U_ANGL_B Phase B angle
VPHMMXU.1.U_ANGL_C Phase C angle
Three-phase voltage (phase-to-
phasevoltages) (RMS)
(VPPMMXU)
Analog inputs VPPMMXU.1.U_DB_AB Phase A to B amplitude,
magnitude of reported value
VPPMMXU.1.U_DB_BC Phase B to C amplitude,
magnitude of reported value
VPPMMXU.1.U_DB_CA Phase C to A amplitude,
magnitude of reported value
VPPMMXU.1.U_ANGL_AB Phase A to B angle
VPPMMXU.1.U_ANGL_BC Phase B to C angle
VPPMMXU.1.U_ANGL_CA Phase C to A angle
Sequence voltage (VSMSQI) Analog inputs VSMSQI.1.U1_DB Positive sequence voltage
amplitude, reported value
VSMSQI.1.U2_DB Negative sequence voltage
amplitude, reported value
VSMSQI.1.U1_ANGL_INST Positive sequence voltage
angle, instantaneous value
VSMSQI.1.U2_ANGL_INST Negative sequence voltage
angle, instantaneous value
Residual current (RESCMMXU) Analog inputs RESCMMXU.1.I0_DB Residual current RMS,
magnitude of reported value
RESCMMXU.1.I0_ANGL Residual current angle
Residual voltage (RESVMMXU) Analog inputs RESVMMXU.1.U0_MAG_DB U0 Amplitude, magnitude of
reported value
Table continues on next page