Function name Signal type Signal name Description
RESVMMXU.1.U0_ANGL_INST U0 angle, instantaneous value
RESVMMXU.1.U0_RMS_DB U0 RMS, magnitude of reported
value
Three-phase non-directional
overcurrent, low stage
(PHLPTOC)
Binary inputs PHLPTOC.1.ST_A Started phase A
PHLPTOC.1.ST_B Started phase B
PHLPTOC.1.ST_C Started phase C
PHLPTOC.1.START Started signal
PHLPTOC.1.OPR_A Operated phase A
PHLPTOC.1.OPR_B Operated phase B
PHLPTOC.1.OPR_C Operated phase C
PHLPTOC.1.OPERATE Operated
Three-phase non-directional
overcurrent, high stage
(PHHPTOC)
Binary inputs PHHPTOC.1.ST_A Started phase A
PHHPTOC.1.ST_B Started phase B
PHHPTOC.1.ST_C Started phase C
PHHPTOC.1.START Started signal
PHHPTOC.1.OPR_A Operated phase A
PHHPTOC.1.OPR_B Operated phase B
PHHPTOC.1.OPR_C Operated phase C
PHHPTOC.1.OPERATE Operated
Three-phase non-directional
overcurrent, instantaneous
stage (PHIPTOC)
Binary inputs PHIPTOC.1.ST_A Started phase A
PHIPTOC.1.ST_B Started phase B
PHIPTOC.1.ST_C Started phase C
PHIPTOC.1.START Started signal
PHIPTOC.1.OPR_A Operated phase A
PHIPTOC.1.OPR_B Operated phase B
PHIPTOC.1.OPR_C Operated phase C
PHIPTOC.1.OPERATE Operated
Negative-sequence overcurrent
(NSPTOC)
Binary inputs NSPTOC.1.START Start Signal
NSPTOC.1.OPERATE Operate Signal
Phase discontinuity
(PDNSPTOC)
Binary inputs PDNSPTOC.1.START Phase discontinuity protection
started
PDNSPTOC.1.OPERATE Phase discontinuity protection
operated.
Three-phase thermal overload
for feeder (T1PTTR)
Binary inputs T1PTTR.1.OPERATE Operate Signal
T1PTTR.1.START Start Signal
Table continues on next page
Section 2 1MRS756791 A
DNP3 data mappings
28 630 series
Point List Manual