DNP3 device profile document
Count > 1 Never Always Sometimes Configurable
Pulse on Never Always Sometimes Configurable
Pulse off Never Always Sometimes Configurable
Latch on Never Always Sometimes Configurable
Latch off Never Always Sometimes Configurable
Queue Never Always Sometimes Configurable
Clear queue Never Always Sometimes Configurable
Explanation of 'Sometimes' above: Supported binary output control operations depend on the type of point. Please consult the binary
output point list description.
Reports binary input change events when no specific variation
requested:
Reports time-tagged binary input change events when no specific
variation requested:
Never Never
Only when time-tagged Binary input change with time
Only non-time-tagged Binary input change with relative time
Configurable to send one or the other
(Obj2DefVar on DNP3Master)
Configurable (Obj2DefVar on DNP3Master)
Sends unsolicited responses: Sends static data in unsolicited responses:
Never Never
Configurable (UREnable on
DNP3Master)
When device restarts
Only certain objects When status flags change
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
function codes supported
No other options are permitted.
Default counter object/variation: Counters roll over at:
No counters reported No counters reported
Configurable (obj20DefVar and
obj22DefVar in DNP3Master)
Configurable (attach explanation)
Default object
Default variation:
16 bits
Point-by-point list attached 32 bits
Other value: _______
Point-by-point list attached
Sends multi-fragment responses:
Yes
No
Configurable (ApplMultFrgRes on DNP3Master)
Deadbanding is not performed in the DNP protocol stack. Any deadbanding is a property of the IED’s underlying data, and is configured
through the IED configuration tools.
● = Selected,○ = Not selected
1MRS756791 A Section 3
DNP3 protocol implementation
630 series 43