24 Start-up and control with I/O
Select the application macro according to which the
control cables are connected.
Continue with the application set-up. After
completing a set-up task, the Start-up assistant
suggests the next one.
Press (when is highlighted) to
continue with the suggested task.
Press key to highlight and then press
to move to the following task without doing the
suggested task.
Press to stop the Start-up assistant.
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
If the drive is in remote control (REM shown on the
status line), switch to local control by pressing .
If you are not in the Output mode, press
repeatedly until you get there.
Increase the frequency reference from zero to a
small value with key .
Press to start the motor.
Check that the actual direction of the motor is the
same as indicated on the display ( means
forward and reverse).
Press to stop the motor.
To change the direction of the motor rotation:
If parameter 9914 PHASE INVERSION is not
visible, first set parameter 1611 PARAMETER
VIEW to 3 (LONG VIEW).
Invert the phases by changing the value of
parameter 9914 to the opposite, ie from 0 (NO) to
1 (YES), or vice versa.
Verify your work by applying input power and
repeating the check as described above.
Set parameter 1611 back to 2 (SHORT VIEW).
9902 APPLIC MACRO
CANCEL SAVE
00:00
PAR EDIT
[1]
ABB STANDARD
REM