30 Actual signals and parameters in the short view
13 ANALOG INPUTS Analog input signal processing
1301 MINIMUM AI1 Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI1. When used as a
reference, the value corresponds to the reference minimum
setting.
020 mA 0100%
420 mA 20100%
-1010 mA -5050%
Example: If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
parameter 1104 REF1 MIN.
Note: MINIMUM AI1 value must not exceed MAXIMUM AI
value.
1.0%
-100.0
100.0%
Value in percent of the full signal range.
Example: If the minimum value for analog input is 4 mA, the
percent value for 020 mA range is:
(4 mA / 20 mA) · 100% = 20%
1 = 0.1%
14 RELAY OUTPUTS Status information indicated through relay output, and relay
operating delays. For more information, see chapter Actual
signals and parameters in ACS310 Users Manual
(3AUA0000044201 [English]).
1401 RELAY
OUTPUT 1
Selects a drive status indicated through relay output RO 1.
The relay energizes when the status meets the setting.
FAULT(-1)
NOT SEL Not used 0
READY Ready to function: Run enable signal on, no fault, supply
voltage within acceptable range and emergency stop signal
off.
1
RUN Running: Start signal on, Run enable signal on, no active
fault.
2
FAULT(-1) Inverted fault. Relay is de-energized on a fault trip. 3
PFC Start/stop motor in PFC control. See parameter group 81
PFC CONTROL in ACS310 Users Manual
(3AUA0000044201 [English]). Use this option only when
PFC control is used. Selection activated/deactivated when
the drive is not running.
31
16 SYSTEM
CONTROLS
Parameter view, Run enable, parameter lock etc.
1611 PARAMETER
VIEW
Selects the parameter view, ie which parameters are shown
on the control panel.
SHORT
VIEW
FLASHDROP Shows the FlashDrop parameter list. Does not include the
short parameter list. Parameters which are hidden by the
FlashDrop device are not visible.
FlashDrop parameter values are activated by setting
parameter 9902 APPLIC MACRO to 31 (LOAD FD SET).
1
SHORT VIEW Shows only those signals and parameters that are listed in
this table and the table in section Actual signals in the short
parameter view on page 29.
2
LONG VIEW Shows all signals and parameters. See chapter Actual
signals and parameters in ACS310 Users Manual
(3AUA0000044201 [English]).
3
Parameters in the short parameter view
No. Name/Value Description Def/FbEq