Technical data 37
Power cable sizes and fuses
Note: Larger fuses must not be used.
Type Fuses Size of copper conductor in cablings
ACS310- gG UL Class T
(600 V)
Supply
(U1, V1, W1)
Motor
(U2, V2, W2)
PE
x = E/U
A A mm
2
AWG mm
2
AWG mm
2
AWG
3-phase U
N
= 200...240 V (200, 208, 220, 230, 240 V)
03x-02A6-2 10 10 2.5 14 1.5 14 2.5 14
03x-03A9-2 10 10 2.5 14 1.5 14 2.5 14
03x-05A2-2 10 15 2.5 14 1.5 14 2.5 14
03x-07A4-2 16 15 2.5 12 1.5 14 2.5 12
03x-08A3-2 16 15 2.5 12 1.5 14 2.5 12
03x-10A8-2 16 20 2.5 12 2.5 12 2.5 12
03x-14A6-2 25 30 6.0 10 6 10 6.0 10
03x-19A4-2 25 35 6.0 10 6 10 6.0 10
03x-26A8-2 63 60 10.0 8 10 8 10.0 8
03x-34A1-2 80 80 16.0 6 16 6 16.0 6
03x-50A8-2 100 100 25.0 2 25 2 16.0 4
3-phase U
N
= 380...480 V (380, 400, 415, 440, 460, 480 V)
03x-01A3-4 10 10 2.5 14 1.5 14 2.5 14
03x-02A1-4 10 10 2.5 14 1.5 14 2.5 14
03x-02A6-4 10 10 2.5 14 1.5 14 2.5 14
03x-03A6-4 10 10 2.5 12 1.5 14 2.5 12
03x-04A5-4 16 15 2.5 12 1.5 14 2.5 12
03x-06A2-4 16 15 2.5 12 1.5 14 2.5 12
03x-08A0-4 16 20 2.5 12 1.5 14 2.5 12
03x-09A7-4 20 25 2.5 12 2.5 12 2.5 12
03x-13A8-4 25 30 6.0 10 6 10 6.0 10
03x-17A2-4 35 35 6.0 8 6 8 6.0 8
03x-25A4-4 50 50 10.0 8 10 8 10.0 8
03x-34A1-4 80 80 16.0 6 16 6 16.0 6
03x-41A8-4 100 100 25.0 4 16 4 16.0 4
03x-48A4-4 100 100 25.0 4 25 4 16.0 4
00578903.xls D