Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
EMBEDDED
FIELDBUS
(Continued)
DATA I/O 4 (58.104) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Denes the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400004.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 5 (58.105) Default: 4 (SW 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Denes the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400005.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 6 (58.106) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Denes the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400006.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 7 (58.107) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400007.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 8 (58.108) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400008.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 9 (58.109) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400009.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 10 (58.110) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400010.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 11 (58.111) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400011.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 12 (58.112) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400012.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 13 (58.113) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400013.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 14 (58.114) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400014.
For the selections, see parameter 58.101 Data I/O 1.