12-12 Startup Assistant & Parameters 3AXD50000011888
Table 12-2 Drive Assistant
Highlight the operating mode suitable to the
application and press save.
Press (save) to select.
If mode was changed, cycle power to drive after
setup is complete.
[1] 2-Wire
[7
]
3-Wire
[8] PID
[9] Fieldbus
00
:
00
Save
Cancel
CTDD 50.0 rpmLocal
76.03 Operating Mode
Additional Settings & Parameter Backup
Trickle Current Function
Primary purpose is to prevent fan rotation during
standby condition and to prevent condensation
in the motor. Use the to enable the function in
software. Highlight enable or eldbus and press
(save). Use to highlight trickle power and
to set the level. Refer to Chapter 10 or parameter
group 74 for proper setup of this function. When
nished, press (next) to continue.
00:00Back
50.0 rpmLocal
Trickle Current
Set parameters for Trickle Current.
Enable
Trickle Power
Next
Disabled
100W
CTDD
Trickle Time Delay 1 min
Trickle Selection
Select the I/O or Communication Link that will
Enable the Trickle Current Function.
If you select “ENABLE”, the Trickle Current Function
will be Enabled whenever the Drive is not running.
[1] ENABLE
[0
]
DISABLE
[2] DI01
[3] FBA
00
:
00 SaveCancel
CTDD 0.0 rpmLocal
74.01 Trickle Selection
[4] EFB
De-Ice
This is a Cooling Tower mode to run the tower in
reverse at a slow speed to prevent ice build up. Use
the to highlight the setting and to access
level values.
Refer to Chapter 10 or parameter group
75 for proper setup. When nished, press
(next) to continue.
00:00Back
50.0 rpmLocal
De-Ice
Set parameters for De-ice.
Enable
De-Ice Speed
Run Time
Minimum torque 1
Next
Disabled
30%
1 min
-30.0 %
CTDD