168 Parameters
Slot 3 Slot 3. 3
4…254 Node ID of the slot on the FEA-03 extension adapter. 1 = 1
14.03 Module 1 status Displays the status of I/O extension module 1. No option
No option No module detected in the specified slot. 0
No communication A module has been detected but cannot be communicated
with.
1
Unknown The module type is unknown. 2
FIO-01 An FIO-01 module has been detected and is active. 15
FIO-11 An FIO-11 module has been detected and is active. 20
FAIO-01 An FAIO-01 module has been detected and is active. 24
14.05 DI status (Visible when 14.01 Module 1 type = FDIO-01)
Displays the status of the digital inputs on the extension
module. The activation/deactivation delays (if any are
specified) are ignored. A filtering time (for input mode) can be
defined by parameter 14.08 DI filter time.
Bit 0 indicates the status of DI1.
Note: The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example: 0101b = DI1 and DI3 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b Status of digital inputs. 1 = 1
14.05 DIO status (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Displays the status of the digital input/outputs on the
extension module. The activation/deactivation delays (if any
are specified) are ignored. A filtering time (for input mode) can
be defined by parameter 14.08 DIO filter time.
Bit 0 indicates the status of DIO1.
Note: The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example: 1001b = DIO1 and DIO4 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b Status of digital input/outputs. 1 = 1
14.06 DI delayed status (Visible when 14.01 Module 1 type = FDIO-01)
Displays the delayed status of the digital inputs on the
extension module. The word is updated only after
activation/deactivation delays (if any are specified).
Bit 0 indicates the status of DI1.
Note: The number of active bits in this parameter depends on
the number of digital inputs on the extension module.
Example: 0101b = DI1 and DI3 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b Delayed status of digital inputs. 1 = 1
No. Name/Value Description Def/FbEq16