Quick start-up guide for ACS880 drives with primary control program 17
Highlight Parameters and press
(Select).
Highlight Complete list using and
and press (Select).
A listing of parameter groups is displayed.
Highlight parameter group 95 HW
configuration and press (Select).
Note that the list wraps around in either
direction between groups 99 and 01. In this
case, it is quicker to use to locate group
95 on the list.
After selecting a group, a listing of
parameters within the group is displayed.
Highlight parameter 95.01 Supply voltage
(if not already highlighted) and press
(Edit).
The available parameter settings are listed.
Local 0.0 rpm
Parameters
Favorites
By function
Back
12:36
Select
Complete list
Modified
Local 0.0 rpm
Complete list
01 Actual values
03 Input references
04 Warnings and faults
05 Diagnostics
06 Control and status words
07 System info
Back
12:36
Select
Local 0.0 rpm
95 HW configuration
95.01 Supply voltage
Back
12:36
Edit
95.02 Adaptive voltage limits
95.04 Control board supply
Not given
Disable
Internal 24V
Local 0.0 rpm
95.01 Supply voltage
[0] Not given
[1] 208…240 V
Cancel
12:36
Save
[2] 380…415 V
[3] 440…480 V
[4] 500 V