5
1
1
Make sure that the insulating parts of the
switchgear are not damaged when the
apparatus is handled.
Before proceeding with any operation, always
make sure that the springs of the operating
mechanism are discharged and that the
switchgear is on the ground.
Keep the switchgear in the horizontal position
when it is handled.
3. Storage
The switchgear must be stored in a dry, dust-free, non-
corrosive place at a temperature between – 5 °C and 45
°C for the standard version and between – 40 °C e + 45 °C
for the low temperature version. Please consult us if special
requirements are involved.
The switch-disconnectors will have been strapped to the
wooden pallet. Cut the strap to unload the equipment.
For handling purposes, the switch-disconnector can be lifted
by a crane fitted with ropes and snap hooks conforming to
the safety standards, to be fastened to the two anchor points
provided. The switch-disconnector can also be shifted by
hand. In this case, lift it by the operating mechanism part on
one side and from the eyebolts (1) on the other side. Switch-
disconnectors weigh approximately 75 kg.