VIKTIGA SÄKERHETSANVISNINGAR 115
FARA
RISK FÖR BAKSPÄNNING! STÄNG AV UPS-SYSTEMET OCH INSTALLERA
EN EXTERN BRYTARE MELLAN NÄTINGÅNGEN OCH UPS-SYSTEMET.
KONTROLLERA ATT DET INTE FINNS NÅGRA LIVSFARLIGA SPÄNNINGAR
FÖRE ARBETE PÅ DENNA KRETS.
FARA
FÖR ATT MINSKA BRANDRISKEN, ANSLUT ENHETEN ENDAST TILL EN KRETS
FÖRSEDD MED ÖVERSTRÖMSSKYDD SOM SKYDDAR MOT:
• D-KURVA 10 A MÄRKSTRÖM (UPPSTRÖMS KRETS),
FÖR 1 kVA-MODELLER (B/S)
• D-KURVA 16 A MÄRKSTRÖM (UPPSTRÖMS KRETS),
FÖR 2 kVA-MODELLER (B/S)
• D-KURVA 20 A MÄRKSTRÖM (UPPSTRÖMS KRETS).
FÖR 3 kVA-MODELLER (B/S).
FARA
HÖG LÄCKSTRÖM:
SE TILL ATT JORDKABELN ÄR ANSLUTEN.
GEMENSAM ANSLUTNING AV IN-/UTKÄLLOR
VARNING
INNAN EN ANSLUTNING UPPRÄTTAS KONTROLLERAR DU ATT
SKYDDSENHETERNA UPPSTRÖMS (NORMALT VÄXELSTRÖMSKÄLLA OCH
FÖRBIKOPPLINGSVÄXELSTRÖMSKÄLLOR) ÄR ÖPPNA ”0” (AV).
VARNING
KONDENSVATTEN KAN UPPSTÅ OM UPS-SYSTEMET PACKAS UPP VID
MYCKET LÅGA TEMPERATURER. VÄNTA I SÅ FALL TILLS UPS-SYSTEMET
HAR TORKAT HELT PÅ IN- OCH UTSIDAN INNAN DET INSTALLERAS ELLER
ANVÄNDS. VÄNTA TILLS UPS-SYSTEMET ÄR FULLSTÄNDIGT TORRT PÅ BÅDE
INSIDAN OCH UTSIDAN FÖRE INSTALLATIONEN FÖR ATT UNDVIKA RISKER
OCH ELEKTRISKA STÖTAR.
VARNING
INDUKTIVA FÖRBRUKARE, T.EX. BILDSKÄRMAR OCH LASERSKRIVARE,
HAR EN MYCKET HÖG STARTSTRÖM. OM SÅDANA FÖRBRUKARE ÄR
ANSLUTNA TILL UPS-SYSTEMET MÅSTE HÄNSYN TAS TILL STARTSTRÖMMEN
NÄR UPS-KAPACITETEN BERÄKNAS. DETTA FÖR ATT FÖRHINDRA ATT
UPS-SYSTEMET ÖVERBELASTAS OCH STÄNGS AV.
OBS!
FÖR ATT UNDVIKA BRANDRISK SKA UPS-SYSTEMET ANSLUTAS TILL
EN KRETS SOM HAR ETT ÖVERLASTSKYDD MED AMPERETAL ENLIGT
STANDARDEN IEC/EN 60934 ELLER ENLIGT DE LOKALA ELEKTRISKA
BESTÄMMELSERNA.
SE DE TEKNISKA SPECIFIKATIONERNA FÖR REKOMMENDATIONER.