Brian PrestonSep 9, 2025
Why does my ABB UPS show display mode code 1?
- RRodney McknightSep 9, 2025
If your ABB UPS displays mode code 1 on the LCD, even when power is available, it means the inverter is not switched on. Press the On-Switch “I”.

Why does my ABB UPS show display mode code 1?
If your ABB UPS displays mode code 1 on the LCD, even when power is available, it means the inverter is not switched on. Press the On-Switch “I”.
Why is the emergency supply period shorter than expected on my ABB UPS?
A shorter than expected emergency supply period on your ABB UPS could be due to batteries that are not fully charged or are defective. Try charging the batteries for at least 5-8 hours and then check their capacity. If the problem continues, it is recommended to consult your dealer.
How to troubleshoot an ABB PowerValue 11 T UPS with no indication or warning tone?
If your ABB UPS has no indication or warning tone even when connected to the mains power supply, the issue might be due to a lack of input voltage. Check the building wiring socket outlet and the input cable.
What to do if my ABB UPS LCD shows code 3 and beeps?
If your ABB UPS LCD shows code 3 and an audible alarm sounds (1 beep every 4 seconds), it indicates that the mains power supply has failed, or the input power and/or frequency are out of tolerance. The system automatically switches to battery mode. Check the input power source; if the problem persists, contact your dealer.
How to fix high inverter temperature in ABB PowerValue 11 T?
If the inverter temperature is high in your ABB UPS, it means the internal temperature is too high. Check the ventilation around the UPS and the ambient temperature of the room.
What causes high DC-DC temperature in ABB UPS?
High DC-DC temperature in your ABB UPS indicates that the internal temperature of the UPS is too high. You should check the ventilation of the UPS and the ambient temperature.
What does 'bus short' mean on my ABB PowerValue 11 T UPS?
If your ABB UPS indicates a 'bus short', it signifies an internal fault within the UPS. Notify your dealer.
What does 'over temperature fault' mean on my ABB UPS?
If your ABB UPS displays 'over temperature fault', it means there's an over temperature condition. Check the ventilation of the UPS and verify the ambient temperature and ventilation in the surrounding area.
What does 'site fail' mean on my ABB PowerValue 11 T UPS?
If your ABB UPS displays 'site fail,' it indicates that the phase and neutral conductors at the input of the UPS system are reversed. Rotate the mains power socket by 180° or correctly connect the UPS system.
What to do if my ABB PowerValue 11 T UPS shows an inverter short?
If your ABB UPS indicates an inverter short, remove all connected loads and turn off the UPS. Check the UPS output and the loads for any short circuits. After ensuring the short circuit is resolved and the UPS has no internal faults, you can turn it on again.
| Model | PowerValue 11 T Series |
|---|---|
| Frequency | 50/60 Hz |
| Output Voltage | 220/230/240 Vac (single phase) |
| Battery Type | Sealed Lead-Acid (SLA) |
| Communication Ports | RS-232, USB |
| Operating Temperature | 0-40°C |
| Dimensions (HxWxD) | Varies by model |
| Weight | Varies by model |
Essential safety measures for users operating the UPS.
Guidelines for battery testing, maintenance, and disposal.
Criteria for selecting an optimal installation location.
Process for putting the UPS into service by authorized personnel.
Instructions for connecting the UPS to the main power supply.
Methods for diagnosing and fixing UPS faults.