Appendix A
CS141 SNMP card available parameters (valid for
CS141 Basic, CS141 ModBus, CS141 Advanced).
The parameters available for CS141 SNMP cards
are shown below.
Parameter Units Type Available interface Modbus register
Measurement Parameters
Input Voltage V Input Webserver / Modbus 104
Input Frequency Hz Input Webserver / Modbus 111
Output Voltage V Output Webserver / Modbus 97
Output Load Percentage % Output Webserver / Modbus 100
Battery Voltage V Battery Webserver / Modbus 110
Battery Capacity % Battery Webserver / Modbus 103
Temperature °C Environmental Webserver / Modbus 107
UPS Status Information
On shutdown Webserver / Modbus 109
On inverter Webserver / Modbus 109
On battery Webserver / Modbus 109
UPS Alarms
Battery Low Webserver / Modbus 117
Input Bad Webserver / Modbus 120
On Bypass Webserver / Modbus 123
General Fault Webserver / Modbus 132
Test In Progress Webserver / Modbus 138
Shutdown imminent Webserver / Modbus 137
Diagnose test failed Webserver / Modbus 133
APPENDIX A