Logic
Table 97. Tripping logic common 3-phase output SMPPTRC
Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater
Evolving fault delay (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Table 98. Number of SMPPTRC instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
SMPPTRC
12 - -
Table 99. Number of SMAGAPC instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
SMAGAPC 12 - -
Table 100. Number of STARTCOMB instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
STARTCOMB 32 - -
Table 101. Number of TMAGAPC instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
Table 102. Number of ALMCALH instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
ALMCALH - - 5
Table 103. Number of WRNCALH instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
WRNCALH - - 5
Table 104. Number of INDCALH instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
INDCALH - 5 -
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
ABB 101