EasyManua.ls Logo

ABB REL670 - Page 115

ABB REL670
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware
IED
Table 166. Case
Material Steel sheet
Front plate Stainless steel with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)
Table 167. Water and dust protection level according to IEC 60529
Front IP40 (IP54 with sealing strip)
Sides, top and bottom IP40
Rear side IP20 with screw compression type
IP10 with ring lug terminals
Table 168. Weight
Case size
Weight
6U, 1/2 x 19”
£ 10 kg/22 lb
6U, 3/4 x 19”
£ 15 kg/33 lb
6U, 1/1 x 19”
£ 18 kg/40 lb
Electrical safety
Table 169. Electrical safety according to IEC 60255-27
Equipment class I (protective earthed)
Overvoltage category III
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
Connection system
Table 170. CT and VT circuit connectors
Connector type
Rated voltage and current Maximum conductor area
Screw compression type 250 V AC, 20 A
4 mm
2
(AWG12)
2 x 2.5 mm
2
(2 x AWG14)
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A
4 mm
2
(AWG12)
Table 171. Auxiliary power supply and binary I/O connectors
Connector type
Rated voltage Maximum conductor area
Screw compression type 250 V AC
2.5 mm
2
(AWG14)
2 × 1 mm
2
(2 x AWG18)
Terminal blocks suitable for ring lug terminals 300 V AC
3 mm
2
(AWG14)
Because of limitations of space, when ring
lug terminal is ordered for Binary I/O
connections, one blank slot is necessary
between two adjacent IO modules. Please
refer to the ordering particulars for details.
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
ABB 115

Other manuals for ABB REL670

Related product manuals