Loading...
Station communication, remote end
serial communication and time
synchronization
Ordering no #11 Notes and rules
Slot position (front view/rear view)
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
The maximum number
and type of LDCM
modules supported
depend on the total
amount of I/O and
communication modules
in the IED.
Available slots in 1/2, 3/4 and 1/1 case
with 1 TRM
Available slots in 3/4 and 1/1 case
with 2 TRM
No communication board included X X X X X X X X X X X X
Optical Ethernet SFP 1MRK005500-AA K K K K K K Optical Ethernet SFP is
basic in P30:1. P30:6:1
and P30:6:2 require the
Optical Ethernet module
in P30:6.
Optical Ethernet module 1MRK002266-EA H
Serial SPA/LON/DNP/IEC
60870-5-103 plastic interface
1MRK001608-AB L
Serial SPA/LON/DNP/IEC
60870-5-103 plastic/glass interface
1MRK001608-BB M
Serial SPA/LON/DNP/IEC
60870-5-103 glass interface
1MRK001608-CB N
Galvanic RS485 communication
module
1MRK002309-AA G G G G
Optical short range LDCM 1MRK002122-AB A A A A A A Max 2 LDCMs can be
ordered. Always place
LDCM modules on the
same board to support
redundant
communication: P30:5,
P30:6, P31:3 or P32:2
and P32:3.
Optical medium range, LDCM 1310
nm
1MRK002311-AA B B B B B B
Optical long range, LDCM 1550 nm 1MRK002311-BA C C C C C C
Line data communication, default
64kbps mode
X Default if no LDCM is
selected
Allow line data communication in
2Mbps mode
1MRK007002-AA Y
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization module 1MRK002305-AA F F F F
Selection for
position #11
K
1MRK 506 372-BEN -