EasyManua.ls Logo

ABB REL670 - Page 56

ABB REL670
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 16. BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ±20%
RL ±20%
RL ±20%
RL ±20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
-
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
Debounce filter Settable 1-20 ms
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
Table 17. IOM - Binary input/output module
Quantity Rated value Nominal range
Binary inputs 8 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ±20%
RL ±20%
RL ±20%
RL ±20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency 10 pulses/s max
Oscillating signal discriminator Blocking settable 1-40 Hz
Release settable 1-30 Hz
Debounce filter Settable 1-20 ms
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
56 ABB

Other manuals for ABB REL670

Related product manuals