Table 63. Voltage-restrained time overcurrent protection VRPVOC
Function Range or value Accuracy
Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio, overcurrent > 95% -
Operate time, start overcurrent at 0 to 2 x I
set
Min. = 15 ms -
Max. = 30 ms
Reset time, start overcurrent at 2 x I
set
to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start overcurrent at 0 to 10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start overcurrent at 10 x I
set
to 0 Min. = 20 ms
Max. = 35 ms
-
Independent time delay to operate at 0 to 2 x
I
set
(0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Inverse time characteristics,
see tables 180 and 181
13 curve types See tables 180 and 181
Minimum operate time for inverse time
characteristics
(0.00 - 60.00) s ±0.2% or ±35 ms whichever is greater
High voltage limit, voltage dependent
operation
(30.0 - 100.0)% of UBase ±1.0% of U
r
Start undervoltage (2.0 - 100.0)% of UBase ±0.5% of U
r
Reset ratio, undervoltage < 105% -
Operate time start undervoltage at 2 x U
set
to 0 Min. = 15 ms -
Max. = 30 ms
Reset time start undervoltage at 0 to 2 x U
set
Min. = 15 ms -
Max. = 30 ms
Independent time delay to operate,
undervoltage at 2 x U
set
to 0
(0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Internal low voltage blocking (0.0 - 5.0)% of UBase ±0.25% of U
r
Overcurrent:
Critical impulse time
Impulse margin time
10 ms typically at 0 to 2 x I
set
15 ms typically
-
Undervoltage:
Critical impulse time
Impulse margin time
10ms typically at 2 x U
set
to 0
15 ms typically
-
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
82 ABB