EasyManua.ls Logo

ABB REL670 - Page 96

ABB REL670
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 83. Current reversal and weak-end infeed logic for phase segregated communication ZC1WPSCH
Function Range or value Accuracy
Detection level phase to neutral
voltage
(10-90)% of UBase ±0.5% of U
r
Detection level phase to phase
voltage
(10-90)% of UBase ±0.5% of U
r
Reset ratio <105% at (20-90)% of UBase -
Operate time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Coordination time for weak-end
infeed logic
(0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Table 84. Scheme communication logic for residual overcurrent protection ECPSCH
Function
Range or value Accuracy
Scheme type Permissive Underreaching
Permissive Overreaching
Blocking
-
Communication scheme
coordination time
(0.000-60.000) s ±0.2% or ±20 ms whichever is greater
Table 85. Local acceleration logic ZCLCPSCH
Function
Range or value Accuracy
Operate current, LoadCurr (1–100)% of IBase ±1.0% of I
r
Operate current, MinCurr (1–100)% of IBase ±1.0% of I
r
Delay time on pick-up for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
Delay time on drop-off for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
Delay time on pick-up for MinCurr value (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
Table 86. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
Function
Range or value Accuracy
Operate mode of WEI logic Off
Echo
Echo & Trip
-
Operate voltage 3U0 for WEI trip (5-70)% of UBase ±0.5% of U
r
Operate time for current reversal
logic
(0.000-60.000) s ±0.2% or ±30 ms whichever is greater
Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
Coordination time for weak-end
infeed logic
(0.000–60.000) s ±0.2% or ±30 ms whichever is greater
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
96 ABB