Table 23. Environmental tests
Description Type test value Reference
Dry heat test (humidity <50%) • 96 h at +55ºC
• 16 h at +85ºC
IEC 60068-2-2
Cold test • 96 h at -25ºC
• 16 h at -40ºC
IEC 60068-2-1
Damp heat test, cyclic • 6 cycles at +25…55°C, Rh
>93%
IEC 60068-2-30
Storage test • 96 h at -40ºC
• 96 h at +85ºC
IEC 60068-2-48
Motor Protection and Control 1MRS756977 D
REM630
Product version: 1.1 Issued: 2011-05-18
ABB 23