EasyManua.ls Logo

ABB Relion 630 Series - Page 24

ABB Relion 630 Series
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 24. Electromagnetic compatibility tests
Description Type test value Reference
100 kHz and 1 MHz burst
disturbance test
IEC 61000-4-18
IEC 60255-22-1, level 3
Common mode 2.5 kV
Differential mode 1.0 kV
Electrostatic discharge test IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3.2001
Contact discharge 8 kV
Air discharge 15 kV
Radio frequency interference
tests
Conducted, common mode 10 V (rms), f=150 kHz...80
MHz
IEC 61000-4-6
IEC 60255-22-6, level 3
Radiated, pulse-modulated 10 V/m (rms), f=900 MHz ENV 50204
IEC 60255-22-3
Radiated, amplitude-
modulated
10 V/m (rms), f=80...2700
MHz
IEC 61000-4-3
IEC 60255-22-3, level 3
Fast transient disturbance
tests
IEC 61000-4-4
IEC 60255-22-4, class A
All ports 4 kV
Surge immunity test IEC 61000-4-5
IEC 60255-22-5
Communication 1 kV line-to-earth
Binary inputs, voltage
inputs
2 kV line-to-earth
1 kV line-to-line
Other ports 4 kV line-to-earth, 2 kV line-
to-line
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8
1...3 s 1000 A/m
Continuous 300 A/m
Motor Protection and Control 1MRS756977 D
REM630
Product version: 1.1 Issued: 2011-05-18
24 ABB