PID-6993-SETTINGS v1
Table 21: MST1TCP Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddress 0 - 65519 - 1 1 Master address
ValMasterAddr No
Yes
- - Yes Validate source (master) address
MasterIP-Addr 0 - 18 IP
Address
1 0.0.0.0 Master IP-address
MasterIPNetMsk 0 - 18 IP
Address
1 255.255.255.255 Master IP net mask
Obj1DefVar 1:BI
2:BI+Flags
- - 1:BI Object 1, default variation
Obj2DefVar 1:BIEv
2:BIEv+AbsTime
3:BIEv+RelTime
-
- 3:BIEv+RelTime Object 2, default variation
Obj3DefVar 1:DI
2:DI+Flags
- - 1:DI Object 3, default variation
Obj4DefVar 1:DIEv
2:DIEv+AbsTime
3:DIEv+RelTime
-
- 3:DIEv+RelTime Object 4, default variation
Obj10DefVar 1:BO
2:BO+Flags
- - 2:BO+Flags Object 10, default variation
Obj20DefVar 1:CNT32+Flags
2:CNT16+Flags
5:CNT32
6:CNT16
-
- 5:CNT32 Object 20, default variation
Obj22DefVar 1:CNTEv32
2:CNTEv16
5:CNTEv32+Time
6:CNTEv16+Time
-
- 1:CNTEv32 Object 22, default variation
Obj30DefVar 1:AI32Int+Flags
2:AI16Int+Flags
3:AI32Int
4:AI16Int
5:AI32Flt+Flags
6:AI64Flt+Flags
-
- 3:AI32Int Object 30, default variation
Obj32DefVar 1:AIEv32Int
2:AIEv16Int
3:AIEv32Int+Time
4:AIEv16Int+Time
5:AIEv32Flt
6:AIEv64Flt
7:AIEv32Flt+Time
8:AIEv64Flt+Time
- - 1:AIEv32Int Object 32, default variation