Name Values (Range) Unit Step Default Description
tVREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event buffer
timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tVREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event buffer
timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tVREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event buffer
timeout
DelOldBufFull No
Yes
- - No Delete oldest event when buffer is full
ExtTimeFormat LocalTime
UTC
- - UTC External time format
DNPToSetTime No
Yes
- - No Allow DNP to set time in IED
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No
Yes
- - No Time synchronization request after timeout
Averag3TimeReq No
Yes
- - No Use average of 3 time requests
PairedPoint No
Yes
- - Yes Enable paired point
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout
tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer