Table 2: Binary inputs
IEC61850 LN.DO.DA AFL-Common SA name IEC61850 LN Desc, DO Desc, DAName Value
Binary signal transfer supervision
BSTGGIO1.Alm1.stVal BSTGGIO1.SEND_SIG_A Send signal alarm, stVal 1=Send alarm
BSTGGIO1.Alm2.stVal BSTGGIO1.RECV_SIG_A Receive signal alarm, stVal 1=Receive alarm
Circuit breaker related signals (CB pos is found in AI)
CBCILO1.EnaCls.stVal CBXCBR1.ENA_OPEN CBXCBR1, ENA_CLOSE, stVal 1 = Close enabled
CBCILO1.EnaOpn.stVal CBXCBR1.ENA_CLOSE CBXCBR1, ENA_OPEN, stVal 1 = Open enabled
CBCILO1.ItlByPss.stVal CBXCBR1.ITL_BYPASS CBXCBR1, ITL_BYPASS, stVal 1 = Interlocking bypassed
CBCSWI1.Pos.stSeld CBXCBR1.SELECTED CBXCBR1, Switch, general, stSeld 1 = CB control selected
CBXCBR1.BlkCls.stVal CBXCBR1.BLK_CLOSE CBXCBR1, Block closing, stVal 1 = Close blocked
CBXCBR1.BlkOpn.stVal CBXCBR1.BLK_OPEN CBXCBR1, Block opening, stVal 1 = Open blocked
Circuit breaker condition monitoring
CCBRBRF1.OpEx.general CCBRBRF1.TRBU CCBRBRF1, Breaker failure trip (external trip), general 1 = Breaker failure trip
CCBRBRF1.OpIn.general CCBRBRF1.TRRET CCBRBRF1, Operate, retrip (internal trip), general 1 = Operate, re-trip
CCBRBRF1.Str.general CCBRBRF1.CB_FAULT_AL CCBRBRF1, Delayed CB failure alarm, general 1 = Start, timer running
Current circuit supervision
CCRDIF1.Alm.stVal CCRDIF1.ALARM CCRDIF1, Alarm, stVal 1 = Alarm
CCRDIF1.Op.general CCRDIF1.FAIL CCRDIF1, Detection of current circuit failure, general 1 = Failure
Three-phase current limit supervision
CMMXU1.HiAlm.stVal CMMXU1.HIGH_ALARM CMMXU1, High alarm, stVal 1 = High alarm
CMMXU1.HiWrn.stVal CMMXU1.HIGH_WARING CMMXU1, High warning, stVal 1 = High warning
CMMXU1.LoAlm.stVal CMMXU1.LOW_ALARM CMMXU1, Low alarm, stVal 1 = Low alarm
CMMXU1.LoWrn.stVal CMMXU1.LOW_WARING CMMXU1, Low warning, stVal 1 = Low warning
Autorecloser signals
DARREC1.ActRec.stVal DAAREC1.ACTIVE DARREC1, Active reclose status, stVal 1=Reclose active
DARREC1.AROn.stVal DARREC1.AR_ON DARREC1, AR switched On, stVal 1=AR switched On
DARREC1.CBManCls.stVal DARREC1.MAN_CB_CL DARREC1, CB manually closed, stVal 1=CB manually closed
DARREC1.FrqOpAlm.stVal DARREC1.FRQ_OP_ALM DARREC1, Frequent operation counter alarm, stVal 1=Frequent operation alarm
DARREC1.LO.stVal DARREC1.LOCKED DARREC1, Lockout status, stVal 1=Lockout
DARREC1.Op.general DARREC1.CLOSE_CB DARREC1, Operate (close command to XCBR), general 1=Close command to CB
DARREC1.OpOpn.general DARREC1.OPEN_CB DARREC1, Operate (open command to XCBR), general 1=Open command to CB
DARREC1.PrgCutOut.stVal DARREC1.CUTOUT_INPRO DARREC1, Cutout time in progress, stVal 1=Cutout time in progress
DARREC1.PrgDsr.stVal DARREC1.DISCR_INPRO DARREC1, Discrimination time in progress, stVal 1=Discr. time in progress
DARREC1.PrgRec.stVal DARREC1.INPRO DARREC1, In progress status, stVal 1=In progress
DARREC1.PrgRec1.stVal DARREC1.INPRO_1 DARREC1, In progress 1st reclose, stVal 1=In progress
DARREC1.PrgRec2.stVal DARREC1.INPRO_2 DARREC1, In progress 2nd reclose, stVal 1=In progress
DARREC1.PrgRec3.stVal DARREC1.INPRO_3 DARREC1, In progress 3rd reclose, stVal 1=In progress
DARREC1.PrgRec4.stVal DARREC1.INPRO_4 DARREC1, In progress 4th reclose, stVal 1=In progress
DARREC1.PrgRec5.stVal DARREC1.INPRO_5 DARREC1, In progress 5th reclose, stVal 1=In progress
Table continues on next page
1MRS756879 A Section 2
DNP3 data mappings
RED615 11
Point List Manual