IEC61850 LN.DO.DA AFL-Common SA name IEC61850 LN Desc, DO Desc, DAName Value
DARREC1.RdyRec.stVal DARREC1.READY DARREC1, Ready reclose status, stVal 1=Reclose ready
DARREC1.SucRec.stVal DARREC1.SUC_RECL DARREC1, Successful reclose status, stVal 1=Successful reclose
DARREC1.UnsCBCls.stVal DARREC1.UNSUC_CB DARREC1, Unsuccessful CB closing status, stVal 1=Unsuccessful CB closing
DARREC1.UnsRec.stVal DARREC1.UNSUC_RECL DARREC1, Unsuccessful reclose status, stVal 1=Unsuccessful reclose
DARREC1.WtMstr.stVal DARREC1.CMD_WAIT DARREC1, Master signal to follower, stVal 1=Master signal to follower
Directional earth-fault protection signals (3 stages), variant DE02
DEFHPTOC1.Op.general DEFHPDEF1.OPERATE DEFHPDEF1, Operate, general 1 = Operate
DEFHPTOC1.Str.general DEFHPDEF1.START DEFHPDEF1, Start, general 1 = Start
DEFLPTOC1.Op.general DEFLPDEF1.OPERATE DEFLPDEF1, Operate, general 1 = Operate
DEFLPTOC1.Str.general DEFLPDEF1.START DEFLPDEF1, Start, general 1 = Start
DEFLPTOC2.Op.general DEFLPDEF2.OPERATE DEFLPDEF2, Operate, general 1 = Operate
DEFLPTOC2.Str.general DEFLPDEF2.START DEFLPDEF2, Start, general 1 = Start
Non-directional earth-fault and sensitive earth-fault protection signals (4 stages), variant DE03. (EFHPTOC1 also in DE02)
EFHPTOC1.Op.general EFHPTOC1.OPERATE EFHPTOC1, Operate, general 1 = Operate
EFHPTOC1.Str.general EFHPTOC1.START EFHPTOC1, Start, general 1 = Start
EFIPTOC1.Op.general EFIPTOC1.OPERATE EFIPTOC1, Operate, general 1 = Operate
EFIPTOC1.Str.general EFIPTOC1.START EFIPTOC1, Start, general 1 = Start
EFLPTOC1.Op.general EFLPTOC1.OPERATE EFLPTOC1, Operate, general 1 = Operate
EFLPTOC1.Str.general EFLPTOC1.START EFLPTOC1, Start, general 1 = Start
EFLPTOC2.Op.general EFLPTOC2.OPERATE EFLPTOC2, Operate, general 1 = Operate
EFLPTOC2.Str.general EFLPTOC2.START EFLPTOC2, Start, general 1 = Start
Transient/Intermittent earth-fault protection signals (1 stage), variant DE02
INTRPTEF1.Op.general INTRPTEF1.OPERATE INTRPTEF1, Operate, general 1 = Operate
INTRPTEF1.Str.general INTRPTEF1.START INTRPTEF1, Start, general 1 = Start
Alarm LED states
LEDGGIO1.SPCSO1.stVal - Alarm LEDs, LED 1, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO2.stVal - Alarm LEDs, LED 2, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO3.stVal - Alarm LEDs, LED 3, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO4.stVal - Alarm LEDs, LED 4, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO5.stVal - Alarm LEDs, LED 5, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO6.stVal - Alarm LEDs, LED 6, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO7.stVal - Alarm LEDs, LED 7, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO8.stVal - Alarm LEDs, LED 8, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO9.stVal - Alarm LEDs, LED 9, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO10.stVal - Alarm LEDs, LED 10, stVal 1 = LED On, 0 = LED Off
LEDGGIO1.SPCSO11.stVal - Alarm LEDs, LED 11, stVal 1 = LED On, 0 = LED Off Global conditioning signals
LEDPTRC1.Op.general - Global conditioning, Operate, general 1 = Operate (general)
LEDPTRC1.Op.phsA - Global conditioning, Operate, phsA 1 = Operate (phsA)
LEDPTRC1.Op.phsB - Global conditioning, Operate, phsB 1 = Operate (phsB)
Table continues on next page
Section 2 1MRS756879 A
DNP3 data mappings
12 RED615
Point List Manual