Table 3: Class 2 PRIVATE measurand frames 6 and 7 for REM615 variant ME01–03
Index IEC 61850 name Description Default scale Frame No6 Frame No7 Comment
1 LD0.CMMXU1.A.phsA.cVal.mag Phase current A 2.4 x x
2 LD0.CMMXU1.A.phsB.cVal.mag Phase current B 2.4 x x
3 LD0.CMMXU1.A.phsC.cVal.mag Phase current C 2.4 x x
4 LD0.RESCMMXU1.A.res.cVal.mag Residual current 2.4 x x
5 LD0.VMMXU1.A.phsA.cVal.mag Phase-to-ground voltage phase A 2.4 x x n.a in ME01
6 LD0.VMMXU1.A.phsB.cVal.mag Phase-to-ground voltage phase B 2.4 x x n.a in ME01
7 LD0.VMMXU1.A.phsC.cVal.mag Phase-to-ground voltage phase C 2.4 x x n.a in ME01
8 LD0.VMMXU1.A.phsAB.cVal.mag Phase-to-phase voltage phase AB 2.4 x x n.a in ME01
9 LD0.VMMXU1.A.phsBC.cVal.mag Phase-to-phase voltage phase BC 2.4 x x n.a in ME01
10 LD0.VMMXU1.A.phsCA.cVal.mag Phase-to-phase voltage phase CA 2.4 x x n.a in ME01
11 LD0.RESVMMXU1.A.res.cVal.mag Residual voltage 2.4 x x n.a in ME01,02
12 LD0.CSMSQI1.SeqA.c1.cVal.mag Positive sequence current 2.4 x x
13 LD0.CSMSQI1.SeqA.c2.cVal.mag Negative sequence current 2.4 x x
14 LD0.CSMSQI1.SeqA.c3.cVal.mag Zero sequence current 2.4 x x
15 LD0.VSMSQI1.SeqA.c1.cVal.mag Positive sequence voltage 2.4 x x n.a in ME01
16 LD0.VSMSQI1.SeqA.c2.cVal.mag Negative sequence voltage 2.4 x x n.a in ME01
17 LD0.VSMSQI1.SeqA.c3.cVal.mag Zero sequence voltage 2.4 x x n.a in ME01
18 LD0.PEMMXU1.TotW.instMag Active power P 1000 x x n.a in ME01
19 LD0.PEMMXU1.TotVAr.instMag Reactive power Q 1000 x x n.a in ME01
20 LD0.PEMMXU1.TotVA.instMag Apparent power S 1000 x x n.a in ME01
21 LD0.PEMMXU1.TotPF.instMag Power factor 1 x x n.a in ME01
22 LD0.MPTTR1.TmpRI.mag Thermal level 1000 x x
23 LD0.FMMXU1.Hz.mag Frequency measurement 75.0 x x n.a in ME01
24 LD0.CMSTA1.AvAmps1.mag Phase current A -demand value 2.4 x
25 LD0.CMSTA1.AvAmps2.mag Phase current B -demand value 2.4 x
26 LD0.CMSTA1.AvAmps3.mag Phase current B -demand value 2.4 x
unmapped LD0.XRGGIO130.AnIn1.mag RTD input 1 10000 - -
optional
ME01,02 only
unmapped LD0.XRGGIO130.AnIn2.mag RTD input 2 10000 - -
optional
ME01,02 only
unmapped LD0.XRGGIO130.AnIn3.mag RTD input 3 10000 - -
optional
ME01,02 only
unmapped LD0.XRGGIO130.AnIn4.mag RTD input 4 10000 - -
optional
ME01,02 only
unmapped LD0.XRGGIO130.AnIn5.mag RTD input 5 10000 - -
optional
ME01,02 only
unmapped LD0.XRGGIO130.AnIn6.mag RTD input 6 10000 - -
optional
ME01,02 only
unmapped LD0.XRGGIO130.AnIn7.mag RTD input 7 10000 - -
optional
ME01,02 only
unmapped LD0.XRGGIO130.AnIn8.mag RTD input 8 10000 - -
optional
ME01,02 only
1MRS756882 B Section 2
IEC 60870-5-103 data mappings
REM615 19