1MRS750915-MUM
REM 54_
57
Machine Terminal
Technical Reference Manual, General
All range parameters can be set but only one is used. The value of the Input mode
parameter determines which range parameter is used. The Temperature range
parameter also defines the sensor type to be used, e.g. PT100.
Parameter Values Default
Voltage range 0 = 0...1V 0...1 V
1 = 0...5 V
2 = 1...5 V
3 = 0...10 V
4 = 2...10 V
5 = -5...5 V
6 = -10...10 V
Current range 0 = 0...1 mA 0...1 mA
1 = 0...5 mA
2 = 1...5 mA
3 = 0...10 mA
4 = 0...20 mA
5 = 4...20 mA
6 = -1...1 mA
7 = -2.5...2.5 mA
8 = -5...5 mA
9 = -10...10 mA
10 = -20...20 mA
Resistance range 0 = 0...100 0...100
1 = 0...200
2 = 0...500
3 = 0...1000
4 = 0...2000
5 = 0...5000
6 = 0...10000
Temperature
range
0 = Pt100 -45...150 °C Pt100 -45...150 °C
1 = Pt100 -45...600 °C
2 = Pt250 -45...150 °C
3 = Pt250 -45...600 °C
4 = Pt1000 -45...150 °C
5 = Pt1000 -45...600 °C
6 = Ni100 -45...150 °C
7 = Ni100 -45...250 °C
8 = Ni120 -45...150 °C
9 = Ni120 -45...250 °C
10 = Ni250 -45...150 °C
11 = Ni250 -45...250 °C
12 = Ni1000 -45...150 °C
13 = Ni1000 -45...250 °C
14 = Cu10 -45...150 °C
15 = Ni120US -45...150 °C
a
a. In Release 2.5 or later
16 = Ni120US -45...250 °C
a