as an input for voltage transducer. The RTD/
mA module enables the use of the
multipurpose protection functions. These
protection functions can be used for tripping
and alarm purposes based on RTD/mA
measuring data, or analog values
communicated via GOOSE messaging. The
mA outputs can be used for transferring
freely selectable measured or calculated
analog values to devices provided with mA
input capabilities.
The enhanced scalability of the 6U variant
IEDs are intended for optimized medium
voltage metal-clad switchgear applications
where additional binary inputs and outputs
are often required.
All binary input and output contacts are
freely configurable using the signal matrix of
the application configuration function in
PCM600.
Please refer to the Input/output overview
tables, the selection and ordering data and
the terminal diagrams for more detailed
information about the inputs and outputs.
Table 3. Analog input configuration
Analog input
configuration
CT (1/5
A)
CT sensitive
(0.1/0.5 A)
VT RTD/
mA
inputs
mA
outputs
AA 4 1 4 - -
AB 7 - 3 - -
AC 8 - 2 - -
BA 4 1 4 8 4
BB 7 - 3 8 4
BC 8 - 2 8 4
Table 4. Binary input/output options for 4U variants
Binary I/O options
Binary input
configuration
BI BO
Default AA 14 9
With one optional binary I/O
module
AB 23 18
With two optional binary I/O
modules
1)
AC 32 27
1) Not possible if RTD/mA module is selected.
Motor Protection and Control 1MRS756977 D
REM630
Product version: 1.1 Issued: 2011-05-18