ABB RER620 - Section 2 IEC 60870-5-101;104 data mappings

ABB RER620
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
The relay can be connected to an Ethernet-based
communications network via a copper RJ45
(100Base TX) or fiber optic LC (100Base FX) con-
nector or serial network via the RS-485 option that
provides one 4-wire or two 2-wire ports. When the
protection and control relay uses the RS-485 bus
for the serial communication, both two- and four
wire connections are supported. Termination and
pull-up/down resistors can be configured with
jumpers on the communication card so external re-
sistors are not needed.
Modbus implementation supports RTU, ASCII and
TCP modes. Besides standard Modbus functional-
ity, the relay supports retrieval of time-stamped
events, changing the active setting group and up-
loading of the latest fault records. If a Modbus TCP
connection is used, five clients can be connected to
the relay simultaneously. Further, Modbus serial
and Modbus TCP can be used in parallel, and if re-
quired both IEC 61850 and Modbus protocols can
be run simultaneously.
Modbus over TCP/IP is supported with the Ethernet
communications option selected. Besides standard
Modbus functionality such as status and control
operations, the relay supports retrieval of time-
stamped events, uploading of disturbance files and
storing of the latest fault records. For the Modbus
TCP connection, a maximum of five clients can be
connected to the relay simultaneously.
DNP3.0 Level 2+ over TCP/IP is also supported with
the Ethernet communications card option. Another
serial communications option offers programma-
ble RS-232 or RS-485 and fiber-optic (ST) serial
ports. Communication channel redundancy is sup-
ported for DNP3. RER620 listens the DNP master on
both channels - serial and TCP/IP - simultaneously
and responds on both ports. One DNP master is
supported. Status and control, including recloser/
breaker trip/close control, operations are sup-
ported in the Level 2+ implementation. Optional se-
rial (RS-232/RS-485) communication interfaces are
available that support user programmable proto-
cols of DNP3.0 Level 2+, IEC 60870-5-101, PG&E 2179
, and Modbus RTU/ ASCII. Another serial communi-
cations option offers programmable RS-232 or RS-
485 and fiber-optic (ST) serial ports. All serial com-
munication card options include an Ethernet
communications port and an IRIG-B port for dedi-
cated time synchronization network connections.
The companion standards IEC 60870-5-101 (for se-
rial line) and IEC 60870-5-104 (for Ethernet) are de-
rived from the IEC 60870-5 protocol standard defi-
nition. It specifies a functional profile for basic
telecontrol tasks. The protection and control relay
supports both balanced and unbalanced link mode.
The relay supports the time synchronization with a
time-stamping resolution of +/-1 ms:
Ethernet based:
SNTP (primary and secondary server support)
With special time synchronization wiring:
IRIG-B (Inter-Range Instrumentation Group - Time
Code Format B)
In addition, the protection and control relay sup-
ports time synchronization via the following se-
rial communication protocols:
Modbus
DNP3
IEC 60870-5-103

Interfaces/protocols
Ethernet Serial
   Fiber-optic (ST)
 - -
Modbus over TCP/IP - -
 - -
SNTP - -
FTP - -
 - -
 - -
Modbus RTU/ASCII - -
IRIG-B time synchronization - -
 - -
 - -