1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
113
REF4B CBFP signal of REF4B A *) 85 0 2 1
ROV1HIGH START signal from Uo>> stage P 170 94 1 1 1,9
ROV1HIGH TRIP signal from Uo>> stage P 170 91 0 1 1
ROV1INST START signal from Uo>>> stage P 170 96 1 1 1,9
ROV1INST TRIP signal from Uo>>> stage P 170 98 0 1 1
ROV1LOW START signal from Uo> stage P 170 84 1 1 1,9
ROV1LOW TRIP signal from Uo> stage P 170 90 0 1 1
TOL3Dev START signal from 3Ith> P 184 84 1 1 1,9
TOL3Dev TRIP signal from 3Ith> P 184 90 0 1 1
TOL3Dev CBFP signal from 3Ith> A *) 85 0 1 1
UI6High START signal from Z<< stage P 253 109 1 1 1,9
UI6High TRIP signal from Z<< stage P 253 119 0 1 1
UI6High CBFP signal from Z<< stage A *) 85 0 2 1
UI6Low START signal from Z< stage P 253 108 1 1 1,9
UI6Low TRIP signal from Z< stage P 253 118 0 1 1
UI6Low CBFP signal from Z< stage A *) 85 0 2 1
UV3HIGH START signal from 3U<< stage P 166 94 1 1 1,9
UV3HIGH TRIP signal from 3U<< stage P 166 91 0 1 1
UV3LOW START signal from 3U< stage P 166 84 1 1 1,9
UV3LOW TRIP signal from 3U< stage P 166 90 0 1 1
Control functions
CO3DC1 3-state sw. 1 position OC P 253 17 1 1 1,9
CO3DC1 3-state sw. 1 command seqence P 253 9 0 1 1
CO3DC1 3-state sw. 1 open output P 253 10 0 1 1
CO3DC1 3-state sw. 1 close output P 253 11 0 1 1
CO3DC1 3-state sw. 1 opening time P 253 12 0 1 1
CO3DC1 3-state sw. 1 closing time P 253 13 0 1 1
CO3DC1 3-state sw. 1 command status P 253 14 0 1 1
CO3DC1 3-state sw. 1 earthing time P 253 15 0 1 1
CO3DC1 3-state sw. 1 freeing time P 253 16 0 1 1
CO3DC1 3-state sw. 1 position FE P 253 18 1 1 1,9
CO3DC2 3-state sw. 2 position OC P 253 19 1 1 1,9
CO3DC2 3-state sw. 2 command seqence P 253 20 0 1 1
CO3DC2 3-state sw. 2 open output P 253 21 0 1 1
CO3DC2 3-state sw. 2 close output P 253 22 0 1 1
CO3DC2 3-state sw. 2 opening time P 253 23 0 1 1
CO3DC2 3-state sw. 2 closing time P 253 24 0 1 1
CO3DC2 3-state sw. 2 command status P 253 25 0 1 1
CO3DC2 3-state sw. 2 earthing time P 253 26 0 1 1
CO3DC2 3-state sw. 2 freeing time P 253 27 0 1 1
CO3DC2 3-state sw. 2 position FE P 253 28 1 1 1,9
COCB1 Breaker 1 position B 240 160 1 1 1,9
COCB1 Breaker 1 command sequence P 242 201 0 1 1
COCB1 Breaker 1 open output P 242 202 0 1 1
COCB1 Breaker 1 close output P 242 203 0 1 1
COCB1 Breaker 1 opening time P 242 204 0 1 1
COCB1 Breaker 1 closing time P 242 205 0 1 1
COCB1 Breaker 1 command status P 242 206 0 1 1
COCB2 Breaker 2 position P 242 207 1 1 1,9
COCB2 Breaker 2 command sequence P 253 29 0 1 1
COCB2 Breaker 2 open output P 243 201 0 1 1
Table 10.6.-1 Class 1 data signals