EasyManua.ls Logo

ABB RET 543 - Double-Pole Power Outputs (PO); Single-Pole Power Output (HSPO); Single-Pole Power Outputs (PO) and a High-Speed

ABB RET 543
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
49
5.1.8.2. Single-pole power outputs (PO) and a high-speed single-pole
power output (HSPO)
The single-pole power outputs BIO2_7_PO1 and BIO2_7_PO2 as well as the high-
speed single-pole power output PS2_4_HSPO8 are outputs where the object to be
controlled is connected in series with two heavy-duty output relay contacts, see the
figure below. These outputs can be used for tripping purposes and for circuit breaker
and disconnector control.
PO1conn_b
Fig. 5.1.8.2.-1 Single-pole power outputs BIO2_7_PO1 and BIO2_7_PO2, and
the high-speed single-pole power output PS2_4_HSPO8
5.1.8.3. Double-pole power outputs (PO)
The double-pole power outputs BIO2_7_PO3... BIO2_7_PO6 are outputs where the
object to be controlled (e.g. a circuit breaker) is electrically connected between the
two relay contacts, see the figure below. These outputs can be used for tripping
purposes and for circuit breaker and disconnector control.
PO3conn_b
Fig. 5.1.8.3.-1 Double-pole power outputs (PO)
+
-
CB
e.g.
BIO2_7_PO1,
BIO2_7_PO2
+
-
CB
e.g.
BIO2_7_PO3...
BIO2_7_PO6