17. Technical data
Table 6. Dimensions
Description Value
Width frame 177 mm
case 164 mm
Height frame 177 mm (4U)
case 160 mm
Depth 201 mm (153 + 48 mm)
Weight complete IED 4.1 kg
plug-in unit only 2.1 kg
Table 7. Power supply
Description Type 1 Type 2
U
aux
nominal 100, 110, 120, 220, 240 V AC, 50 and
60 Hz
24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
50 ms at U
n
rated
U
aux
variation 38...110% of U
n
(38...264 V AC) 50...120% of U
n
(12...72 V DC)
80...120% of U
n
(38.4...300 V DC)
Start-up threshold 19.2 V DC (24 V DC * 80%)
Burden of auxiliary voltage supply
under quiescent (P
q
)/operating
condition
DC < 12.0 W (nominal)/< 18.0 W (max)
AC< 16.0 W (nominal)/< 21.0W (max)
DC < 12.0 W (nominal)/< 18.0 W (max)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Fuse type T4A/250 V
Transformer Protection and Control 1MRS756891 F
RET615
Product version: 4.0
ABB 25