EasyManua.ls Logo

ABB ret650 - Page 5

ABB ret650
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RET650 A05 - 3 Winding Transformer protection 20AI 2*(6I+4U)
W1
T3W PDIF
87T 3Id/I
CC RBRF
50BF 3I> BF
CC RBRF
50BF 3I> BF
OC4 PTOC
50/51 3I>
OC4 PTOC
51/67 3I>
CC RPLD
52PD PD
CC RBRF
50BF 3I> BF
CC RPLD
52PD PD
EF4 PTOC
51N IN>
CC RPLD
52PD PD
TR PTTR
49 Ith
TR PTTR
49 Ith
V MSQI
Meter.
C MSQI
Meter.
V MMXU
Meter.
C MMXU
Meter.
CV MMXN
Meter.
V MSQI
Meter.
C MSQI
Meter.
V MMXU
Meter.
C MMXU
Meter.
CV MMXN
Meter.
TCS SCBR
Cond
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
TR8 ATCC
90
U
TCM YLTC
84
UV2 PTUV
27 U<
OV2 PTOV
59 U>
PH PIOC
50 3I>>
TR PTTR
49 Ith
REF PDIF
87N IdN/I
Other configured functions
REF PDIF
87N IdN/I
REF PDIF
87N IdN/I
OEX PVPH
24 U/f>
OC4 PTOC
51/67 3I>
EF4 PTOC
51N/67N
IN>
EF4 PTOC
51N/67N
IN>
DRP RDRE
Mont.
CV MMXN
Meter.
Y
Y
@
ROV2 PTOV
59N 3UO>
35 kV Bus
110 kV Bus
10 kV Bus
IEC61850
ANSI IEC
Function On
in Settings
IEC61850
ANSI IEC
Function Off
in Settings
Transformer Data:
40/40/15 MVA
110±11*1.5% / 36.75 / 10.5 kV
210/628/825 A
YNyn0d5
110kV/100V
300/1
1000/1
800/1
800/1
300/1
10kV/100V
35kV/100V
1000/1
W3 W2
IEC09000646-3-en.vsd
IEC09000646 V3 EN
Figure 2. A typical protection application for a three-winding transformer in single breaker arrangement
Transformer protection RET650
1MRK 504 137-BEN B
Product version: 1.3
ABB 5

Other manuals for ABB ret650

Related product manuals