Table 15. Mechanical tests
Description Reference Requirement
Vibration tests (sinusoidal) IEC 60255-21-1 Class 2
Vibration response test: - f = 10…150
Hz - ± 0.075 mm/1.0 g - 1 sweep
cycle in each axis Vibration
endurance test:- f = 10…150 Hz - 2.0
g - 20 sweep cycles in each axis
Shock and bump test IEC 60255-21-2 Class 2
Shock response test:- peak
acceleration 10 g - duration of the
pulse 11 ms - number of pulses in
each direction: 3 .
Shock withstand test: - peak
acceleration 30 g - duration of the
pulse 11 ms - number of pulses in
each dir3 Bump test:- peak
acceleration 20 g - duration of the
pulse 16 ms - number of pulses in
each direction: 1000
Table 16. Contact tests
Description
Type test value Reference
Make and carry Signalling contacts:
5 A, continuous; 8 A for 3 s; 10 A for
0.5 s
IEC 60255-23 and IEC 60255-27
Breaking capacity for d.c., L/R 40 ms Signalling contacts:
48 V, 1 A; 110 V, 0.25 A; 220 V, 0.15
A
IEC 60255-23 and IEC 60255-27
Mechanical durability 10000 operations IEC 60255-6
Table 17. EMC compliance
Description
Reference
EMC directive 2004/108/IEC
Standard EN 50263 (2000)
EN 60255-26 (2007)
Table 18. RoHS compliance
Description
Complies with RoHS directive 2002/95/EC
Remote I/O 1MRS757487 A