Table 13. Electromagnetic compatibility and immunity tests, continued
Description Type test value Reference
Voltage dips, short interruptions and
voltage variation immunity tests (AC
50 Hz and 60 Hz)
30 % reduction for 1 period
60% reduction for 50 periods
100% reduction for 5 periods
100% reduction for 50 periods
IEC 61000-4-11 and IEC 61000-6-5,
level 5
Voltage drop, supply Interruption and
voltage variations on d.c. input power
port (immunity tests)
30% reduction for 0.1 s
60% reduction for 0.1 s
100% reduction for 0.05 s
IEC 61000-4-29 and IEC 61000-6-5
Ripple voltage 10 % Un, 50 and 60 Hz (frequencies
of ripple)
IEC 61000-4-17 and IEC 61000-6-5
Power frequency voltage 50 Hz and
60 Hz
For Input/output port :- Differential
mode ;- 150 V r.m.s., 100 Ω coupling
resistor, 0.1μF coupling capacitor ;
Common mode;- 300V r.m.s., 220Ω
coupling resistor, 0,47 μF coupling
capacitor
IEC 61000-4-16 and IEC 60255-22-7
Emission tests IEC 60255-25
Radiated
30...230 MHz < 40 dB (μV/m) quasi peak,
measured at 10 m distance
230...1000 MHz < 47 dB (μV/m) quasi peak,
measured at 10 m distance
Conducted
0.15...0.50 MHz < 79 dB (μV) quasi peak
< 66 dB (μV) average
0.5...30 MHz < 73 dB (μV) quasi peak
< 60 dB (μV) average
Table 14. Insulation tests
Description
Type test value Reference
Dielectric tests
Test voltage
2 kV, 50 Hz, 1 min
500V, 50 Hz, 1 min, communication
IEC 60255-5 and IEC 60255-27
Impulse voltage tests
Test voltage
5 kV, 1.2/50 μs, 0.5 J,
1 kV, 1.2/50 μs, 0.5 J, communication
IEC 60255-5 and IEC 60255-27
Insulation resistance measurement
Insulation resistance
>100 MΩ, 500 V DC
IEC 60255-5 and IEC 60255-27
Earth leaking current test < 3.5 mA AC
10 mA DC
IEC 60255-27
Mechanical durability of plug-in relays 200 withdrawals and insertions under
deenergized conditions
IEC 60255-6