Table 13. Electromagnetic compatibility and immunity tests
Description Type test value Reference
Electrostatic discharge IEC 61000-4-2, Level 3 and IEC
60255-22-2
Contact discharge 6 kV
Air discharge 8 kV
Radio-frequency electromagnetic
field (amplitude modulated)
10 V/m (rms)
f= 80 - 1000 MHz
IEC 61000-4-3, Level 3 and IEC
60255-22-3
Radio-frequency electromagnetic
field from digital radio telephones
(pulse modulated)
10 V/m (rms)
f = 900 MHz
IEC 61000-4-3, Level 3 and IEC
60255-22-3
Power-frequency (50 Hz) magnetic
field
IEC 61000-4-8, Level 5
Continuous 100 A(rms)/m
1 second 1000 A(rms)/m
Pulse magnetic field 1000A/m; 1.2/50 (8/20) μs Tr/Th; 5
pulses positive/negative; 10 s (time
interval)
IEC 61000-4-9, Level 5
Conducted disturbance induced by
radio frequency fields, Amplitude
modulated
0.15 – 80 MHz - 10 V (unmod., rms);
80% AM (1 kHz); 150 Ohms source
impedance; 27 and 68 MHz (spot
frequencies); 10 V (unmod., rms);
80% AM (1 kHz); 150 Ohms source
impedance
IEC 61000-4-6, Level 3 and IEC
60255-22-6
Fast low energy transient (EFT)
(including functional earth port)
5/50 ns Tr/Th; 2.5 kHz repetition
frequency; 4 kV (peak) for power
supply and input/output ports; 2 kV
(peak) for communication port
IEC 61000-4-4, Level 4 and IEC
60255-22-4
Damped oscillatory waves (HFD) 1
MHz burst
1MHz frequency; 75ns Tr; 400 Hz
repetition frequency; 200 Ohms
source impedance; power supply and
Input/output ports :- Differential
mode : 1 kV (peak); Common mode :
2.5 kV (peak); For communication
port :- differential mode : not
applicable ; common mode : 1 kV
(peak)
IEC 61000-4-12, Level 3 and IEC
60255-22-1
Slow high energy transient
(surge1.2/50 us voltage pulse)
Auxiliary power supply and input/
output ports - ± 4 kVp (L-Gnd) ± 2
kVp (L-L); Communication port - ± 2
kVp (L-Gnd) while no L-L test is
applicable.; 1.2/50 μs Tr/Th (open
circuit); 8/20 μs Tr/Th (short circuit)
IEC61000-4-5, Level 4 and IEC
60255-22-5
Voltage interruption 100% reduction; 2, 5, 10, 20, 50,
100, 200 ms
IEC 60255-11
Remote I/O 1MRS757487 A