Table 8. Signal outputs (Digital output module DOM)
Description Value
Rated voltage 250V AC/DC
Continuous contact carry 5A
Make and carry for 3.0 s 10A
Make and carry for 0.5 s 15A
Breaking capacity when the control-circuit time constant L/
R < 40 ms, at 48/110/220V DC
1A / 0.25A / 0.15A
Table 9. Communication interface (Communication module LECM)
Cable Data transfer
Shielded twisted pait cable, at minimum CAT5e with
RJ-45 connector
10/100 MBits/s
Table 10. Degree of protection by enclosure
Description value
Degree of protection IP20
Table 11. Environmental conditions
Description
Value
Operating temperature range -40...+70ºC
Relative humidity < 93%
Atmospheric pressure 86...106 kPa
Altitude up to 2000 m
Transport and storage temperature range -40...+85ºC
Table 12. Environmental tests
Description
Type test value Reference
Dry heat test 96 h at +70ºC IEC 60068-2-2
Dry cold test 96 h at -40ºC IEC 60068-2-1
Damp heat test, cyclic 6 cycles at +25...55ºC, humidity >
93%
IEC 60068-2-30
Storage test 96 h at +85ºC
96 h at -40ºC
IEC 60068-2-48